Smoke Alarms (Detectors), Specific Location Requirements
The installation of smoke alarms (detectors) must be in accordance with the manufacturer's instructions and NFPA 72, the National Fire Alarm Code. Section 72:11.8.3.5 lists specific location requirements to improve reliability and avoid false alarms. Smoke alarms (detectors) must:
- not be located where the humidity and temperature are outside of the limits specified by the manufacturer,
- not be located where temperatures fall below 40 degrees or exceed 100 degrees,
- be mounted on an inside wall or ceiling where outside walls or ceilings are poorly insulated,
- be photoelectric, or have alarm-silencing, when installed within 20 feet of a cooking appliance,
- not be installed within 36 inches from a door to a kitchen or bathroom containing a shower or tub,
- not be installed within 36 inches from a supply register of a forced hot-air heating or cooling system,
- not be installed within 36 inches from the tip of a blade of a fan suspended from a ceiling,
- be located in a stairway so that an intervening door or obstruction does not prevent rising smoke from reaching the alarm (detector),
- be located on the basement ceiling near the entry to the stairs.

